GB Operating Manual Light control “PULSE HFMD - Vers. III“
GB Operating Manual Light control “PULSE HFMD - Vers. III“
Explanation of the functions (part 5)
Function 20
Follow-up time
Function to adjust the time after
which the light is to be switched off
if no presence is detected.
The default setting of the follow-up
time is 10 min.
6 different follow-up times from 5
to 30 min can be set.
The function can be changed on
lights with sensors XXX
/P
Function 30
Presence range
Function to set the detection range
of the presence sensor.
The default setting for the range of
the presence sensor is 80%.
6 different stages from 10% to
100% can be set.
The function can be changed on
lights with sensors XXX
/P